§ 31-31. IBC CHAPTER 31 SPECIAL CONSTRUCTION - amendments.  


Latest version.
  • Only the following portions of CHAPTER 31 SPECIAL CONSTRUCTION are amended.

    (a) 3103.1.2 Permit required, is amended as follows:

    3103.1.2 Permit required.

    Temporary structures that cover an area greater than 200 square feet (18.58 m ), including connecting areas or spaces with a common means of egress or entrance which are used or intended to be used for the gathering together of 10 or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.

    (b) 3103.2 Construction documents, is amended as follows:

    3103.2 Construction documents.

    A permit application and construction documents shall be submitted for each installation of a temporary structure, temporary tent or other membrane structure. The construction documents shall include:

    1.

    A site plan indicating the size and location of the temporary structure(s), handicap parking and accessible routes.

    2.

    A floor plan showing accessible seating, exit locations, exit pathways and exit width.

    3.

    Occupant load.

    4.

    Information describing any electrical, mechanical and plumbing systems.

    5.

    An affidavit of flame resistance treatment.

    6.

    Bleacher plans complying with ICC300.

    (c) 3103.6 Canopies - residential, is added as follows:

    3103.6 Canopies - residential.

    Canopies rented and used on private residential property are not subject to the above requirements if all the following requirements are met:

    1.

    The canopy is not larger than 400 square feet.

    2.

    Maximum occupant load: 26 with tables and chairs; or 57 with unfixed chairs.

    3.

    The canopy is open on two or more sides.

    4.

    The canopy is removed within 7 days of installation.

    5.

    Electrical, mechanical and plumbing systems shall comply with permit and inspection requirements.

    6.

    The canopy has flame resistance as required by the International Fire Code.

    7.

    The canopy shall comply with city fire and zoning requirements.

    (d) Section 3109 Swimming Pool Enclosures and Safety Devices, is deleted.

(Ord. No. 4284, § 2(Res. No. 10597, § 1, Exh.A), 11-28-16, eff. 1-1-17)